In short
- On 8 August 2025, the government updated its fire door guidance for the Fire Safety (England) Regulations 2022.
- The regulations don't require existing flat entrance doors to meet today's new-build standards.
- An older door can be adequate if it self-closes, fits its frame and isn't damaged or altered.
- Missing strips and seals or a missing certificate don't automatically mean replacement.
Why this question keeps coming up
Since the Fire Safety (England) Regulations 2022 came into force in January 2023, responsible persons in blocks over 11 metres have had to check flat entrance doors at least every 12 months – see fire door inspection requirements for flats.
Some inspectors then treated any door without a modern test certificate or label as non-compliant. Leaseholders were told to replace sound doors, often at a cost of £1,000 to £3,000 or more each, and some freeholders started wholesale replacement programmes that weren't needed.
What the August 2025 fire door guidance says
On 8 August 2025, the Ministry of Housing, Communities and Local Government (MHCLG) updated its guidance on the regulations. It added a new foreword and amended the guidance and checklist. The key points:
- The purpose of the regulations is not to ensure existing flat entrance doors meet current standards for flat entrance doors in new blocks of flats
- The question is whether the door's fire performance is adequate to address the risk to residents from fire
- An older door made to earlier standards may be acceptable even if it has no intumescent strips or smoke seals
- The checklist item on strips and seals is only there to make sure that if they are present, they're undamaged
- The focus is on doors being self-closing, maintained and not damaged
The guidance applies in England.
Certified, notional and nominal fire doors
| Type | What it means | Can it stay? |
|---|---|---|
| Certified | Tested and labelled to a current fire resistance standard, usually FD30S | Yes, if maintained and not altered |
| Notional | Built to a recognised historic specification for fire doors, without a modern test certificate | Often yes, if it closes properly, fits well and is in good condition |
| Nominal / unknown | No evidence of how it was made – judged on its construction and condition | Needs a competent assessment – it may be adequate, or may need upgrading or replacing |
A missing certificate isn't the same as a failed door. What matters is how the door is likely to perform in a fire.
When is an older flat entrance door still adequate?
A competent inspector will usually accept an older door where:
- It self-closes fully and latches from any open position
- It fits its frame, with no excessive gaps at the sides, head or threshold
- The door leaf is solid and hasn't been cut, drilled or patched
- Any glazing is fire-rated and intact
- Letterplates, spy holes and locks haven't compromised the door
- Any intumescent strips and smoke seals that are present aren't damaged or painted over
- It's consistent with the building's evacuation strategy and the fire risk assessment
When does a flat entrance door need replacing?
Replacement – or a certified upgrade – is usually needed when:
- A leaseholder has fitted a non-fire-rated door, such as a standard timber, uPVC or composite front door
- The door can't be made to self-close and latch reliably
- The leaf is damaged, split, hollow-core or has large holes for cat flaps, new locks or cabling
- Gaps are too large to fix with adjustment or minor repairs
- Glazing isn't fire-rated, or there's a non-rated fanlight or side panel
- The frame is damaged or isn't fixed securely to the wall
- The door is a type identified by the government or manufacturer as failing to perform – for example, certain GRP composite doors investigated after Grenfell
Often, the answer is repair, not replacement: adjusting hinges, fitting a self-closer, replacing seals or upgrading a letterplate costs a fraction of a new doorset.
Why self-closers matter most
The single most important check is whether the door closes by itself. The Grenfell Tower Inquiry found that flat entrance doors left open allowed smoke to spread into the stair. A sound older door that shuts is far better than a certified door wedged open or with its closer removed.
Who pays for replacing a flat entrance door?
It depends on the lease:
- Where the door is part of the leaseholder's demise, the leaseholder is usually responsible for repair or replacement
- Where it's part of the building structure or common parts, the freeholder or landlord is usually responsible, and costs may be recoverable through the service charge
- Some leases are unclear – take advice before starting a programme
Whoever owns the door, the responsible person still has duties under the Fire Safety Order and Regulation 10 to check it and act on defects.
What responsible persons should do
- Don't start wholesale replacement based only on missing certificates or labels.
- Get a competent inspection that records each door's construction, condition and defects.
- Prioritise doors that don't self-close or have been replaced with non-fire-rated doors.
- Repair where repair is enough, and replace only where it isn't.
- Feed results into the fire risk assessment, and explain the approach to leaseholders.
- Keep records of inspections, repairs and access attempts.
Our fire door inspections separate doors that genuinely need replacing from those that only need repairs, with a prioritised schedule you can share with leaseholders.
How we can help
We match each project to a qualified specialist and confirm the scope, the named professional and a fixed fee before you commit.
Sources
- GOV.UK – Fire Safety (England) Regulations 2022: fire doors guidance
- FPA – Government issues update to fire door guidance
- CHSG – MHCLG issue update to fire door guidance
This guide is general information based on the law and guidance in England as at 21 November 2026. It isn't legal advice – for advice on a specific building, get in touch.