In short
- AFFF containing PFOA has been banned from use in the UK since 4 July 2025.
- Not every AFFF extinguisher is banned – most foam made in roughly the last ten years uses C6 chemistry without PFOA. But you need evidence.
- Non-compliant units must go to a licensed hazardous waste route – never a skip or a drain.
- HSE has proposed a wider UK ban on all PFAS in firefighting foams, with a likely 5-year phase-out for portable extinguishers.
What is AFFF, and what is PFOA?
AFFF (aqueous film-forming foam) is the foam in most traditional foam fire extinguishers and many fixed foam systems. It's used on Class A (solids such as paper and wood) and Class B (flammable liquids) fires.
AFFF works because it contains PFAS (per- and polyfluoroalkyl substances) – often called "forever chemicals" because they don't break down in the environment. One of them, PFOA (perfluorooctanoic acid), is a persistent organic pollutant. It builds up in people and wildlife and is linked to health and environmental harm.
What the AFFF foam extinguisher ban covers
PFOA, its salts and related compounds are restricted under the Persistent Organic Pollutants (POPs) Regulations, enforced in England by the Environment Agency. Existing firefighting foam was allowed a time-limited exemption. In the UK, that exemption ended on 4 July 2025.
Since then:
- Foam extinguishers and fixed foam systems containing PFOA above the permitted trace limits must not be used, and must be taken out of service
- PFOS and PFHxS – two other "forever chemicals" – were already banned
- Refilling an old PFOA unit with new foam doesn't make it compliant if residues remain above the limits
The EU extended its own deadline to 3 December 2025. The UK didn't – the UK date stayed at 4 July 2025.
Are all foam extinguishers banned?
No. The ban covers foam containing PFOA. Most AFFF made in roughly the last ten years uses C6 (fluorotelomer) chemistry, which doesn't contain PFOA, PFOS or PFHxS. As of late 2025, there was no UK law stopping the supply or refilling of C6 AFFF extinguishers.
But age alone isn't proof. Some guidance suggests extinguishers made since around 2016 are likely to be PFOA-free – you still need evidence for each type of unit.
How to check your foam extinguishers
- List every foam extinguisher and fixed foam system – location, manufacturer, model, date of manufacture and supplier.
- Check the safety data sheet (SDS) for the foam concentrate. Look for PFOA, PFOS or PFHxS.
- Ask your extinguisher servicing company or manufacturer for written confirmation of what the foam contains.
- Consider laboratory testing where you have many units or a fixed foam system, and the paperwork isn't clear.
- If you can't prove a unit is compliant, take it out of service and replace it.
Keep the evidence with your fire safety records. A competent fire risk assessor will ask to see it.
Disposing of non-compliant extinguishers
PFOA foam is hazardous waste. It must not be:
- Put in a general waste skip
- Discharged onto the ground or into drains
- "Test fired" to empty it
Use your extinguisher servicing company or a licensed hazardous waste contractor, and keep the waste transfer documents. For a large site, agree a disposal plan before replacing units.
Replacement options
| Option | Good for | Points to note |
|---|---|---|
| Fluorine-free foam (F3) | Class A and B fires – the closest like-for-like replacement | No PFAS, so it won't be caught by the coming wider restriction |
| Water and water-mist | Class A fires; some water-mist units are rated for other classes | Check the fire classes on the label |
| CO₂ | Electrical equipment and Class B fires | No residue, but little cooling – the fire can reignite |
| Dry powder | Mixed fire risks outdoors or in plant areas | Not recommended in enclosed spaces – it reduces visibility and can be inhaled |
Choose replacements based on the fire risks in each area, not just like for like. Your fire risk assessment should guide this.
The next step: a UK ban on all PFAS in firefighting foams
In August 2025, the Health and Safety Executive (HSE), as the UK REACH Agency, proposed restricting all PFAS in firefighting foams in Great Britain – not just PFOA. Under the proposal:
- Portable fire extinguishers would have a 6-month transition before sales stop, and a 5-year transition before use stops
- Other sectors would get longer or shorter transition periods – up to 10 years for some major hazard sites
- Foams with PFAS above set limits would need labelling and management plans
The public consultation closed in February 2026, and HSE published its risk assessment opinion in July 2026. The final restriction and dates haven't been confirmed yet. If you're replacing foam extinguishers now, fluorine-free foam avoids having to replace them again.
Do blocks of flats need fire extinguishers?
Often, no. National guidance on fire safety in purpose-built blocks of flats generally advises against fire extinguishers in the common parts, because residents should leave the building and call the fire service, not fight the fire. Extinguishers are more often found in plant rooms, bin stores, offices, concierge areas and commercial units.
If your block does have extinguishers in the common parts, your fire risk assessment should say whether they're needed at all.
What responsible persons should do now
- Check every foam extinguisher and fixed foam system for PFOA, and keep the evidence
- Take non-compliant units out of service and dispose of them through a licensed route
- Prefer fluorine-free foam or another suitable type when replacing
- Update your fire safety records and asset registers
- Ask your fire risk assessor to confirm extinguisher provision is appropriate for each area
Our fire risk assessments check portable firefighting equipment as part of the wider review of the building's fire precautions.
How we can help
We match each project to a qualified specialist and confirm the scope, the named professional and a fixed fee before you commit.